ABB limited macro

The ABB limited macro is suitable for an IO-controlled drive which has the minimum
number of I/O available.
The ABB limited macro is optimized for the base drive variant (ACS380-04xN) with no
optional module connected.
You can activate the macro from the Control macros view, or by setting parameter
96.04 Macro select
Default control connections for the ABB limited macro
This is the default control connection diagram for the base drive variant
(ACS380-04xN) with the ABB limited macro selected.
Terminals
Notes:
Terminal sizes: 0.14 mm² ... 1.5 mm²
Tightening torque: 0.5 N·m (0.4 lbf·ft).
Terminals DGND and SGND are internally connected to same reference potential.
Input signals
• Start / Stop (DI1)
• Output frequency or motor speed reference (DI2)
Output signals
• Relay output 1: Fault (-1)
• No Fault [Fault (-1)]
ghv Vertriebs-GmbH | Am Schammacher Feld 47 | 85567 Grafing | Telefon + 49 80 92 81 89 0 | info@ghv.de | www.ghv.de
to value ABB limited 2-wire.
Description
Digital I/O connections
Aux. +24 V DC, max 200 mA
Aux. voltage output common
Digital input common
Stop (0) / Start (1)
Speed (1) / freq selection (2)
Safe torque off (STO)
Safe torque off. Connected at factory.
Drive starts only if both circuits are closed.
Relay output 1
No fault [Fault (-1)]
Control macros
35