Download Print this page

Control Interfaces - ABB ACS380 Firmware Manual

Machinery control program
Hide thumbs Also See for ACS380:

Advertisement

ACS380 FW.book Page 64 Friday, May 4, 2018 4:18 PM
64 Program features

Control interfaces

The number of inputs and outputs depend on the product variant and if the drive is
equipped with any optional I/O extension modules.
S variant:
• 4 x Digital Inputs
• 2 x Digital Inputs/Outputs
• 2 x Analog Inputs
• 1 x Analog Output
• 1 x Relay Output
C variant:
• 2 x Digital Inputs
• 1 x Relay Output
Programmable analog inputs
There are max two programmable analog inputs. Each of the inputs can be
independently set as a voltage (0/2...10 V) or current (0/4...20 mA) input by a switch
on the control unit. Each input can be filtered, inverted and scaled.
Settings
Parameter group
12 Standard AI
Programmable analog outputs
There is max one current (0...20mA) analog output. The output can be filtered,
inverted and scaled.
Settings
Parameter group
13 Standard AO
Programmable digital inputs and outputs
There are max four digital inputs, and two digital inputs/outputs (I/O that can be set as
either an input or an output).
Digital inputs DI3 and DI4 can be used as frequency input and digital outputs DIO1
and DIO2 can be used as frequency output.
Settings
Parameter groups
(page 135).
ghv Vertriebs-GmbH | Am Schammacher Feld 47 | 85567 Grafing | Telefon + 49 80 92 81 89 0 | info@ghv.de | www.ghv.de
(page 141).
(page146).
10 Standard DI, RO
(page 131) and
11 Standard DIO, FI, FO

Hide quick links:

Advertisement

loading