ACS380 FW.book Page 252 Friday, May 4, 2018 4:18 PM
252 Parameters
No.
Name/Value
36

36 Load analyzer

36.01
PVL signal source
Not selected
Motor speed used
Output frequency
Motor current
Motor torque
DC voltage
Output power
Speed ref ramp in
Speed ref ramp out
Speed ref used
Torque ref used
Freq ref used
Process PID out
Other
36.02
PVL filter time
0.00...120.00 s
36.06
AL2 signal source
36.07
AL2 signal scaling
0.00...32767.00
36.09
Reset loggers
Done
ghv Vertriebs-GmbH | Am Schammacher Feld 47 | 85567 Grafing | Telefon + 49 80 92 81 89 0 | info@ghv.de | www.ghv.de
Description
Peak value and amplitude logger settings.
See also section
Load analyzer
(page 104).
Selects the signal to be monitored by the peak value
logger.
The signal is filtered using the filtering time specified by
parameter
36.02 PVL filter
time.
The peak value is stored, along with other pre-selected
signals at the time, into parameters
36.10
The peak value logger can be reset using parameter
36.09 Reset
loggers. The date and time of the last reset
are stored into parameters
36.16
and
None (peak value logger disabled).
01.01 Motor speed
used.
01.06 Output
frequency.
01.07 Motor
current.
01.10 Motor
torque.
01.11 DC
voltage.
01.14 Output
power.
23.01 Speed ref ramp
input.
23.02 Speed ref ramp
output.
24.01 Used speed
reference.
26.02 Torque reference
used.
28.02 Frequency ref ramp
output.
40.01 Process PID output
actual.
Source selection (see
Terms and
abbreviations).
Peak value logger filtering time. See parameter
signal
source.
Peak value logger filtering time.
Selects the signal to be monitored by amplitude logger 2.
The signal is sampled at 200 ms intervals.
The results are displayed by parameters
Each parameter represents an amplitude range, and
shows what portion of the samples fall within that range.
The signal value corresponding to 100% is defined by
parameter
36.07 AL2 signal
scaling.
Amplitude logger 2 can be reset using parameter
Reset
loggers. The date and time of the last reset are
stored into parameters
36.50
and
36.51
For the selections, see parameter
36.01 PVL signal
source.
See parameter
36.01
for the selections.
Defines the monitored signal value for the amplitude
logger AL2 that corresponds to 100% sample value.
Signal value corresponding to 100%.
Resets the peak value logger and/or amplitude logger 2.
(Amplitude logger 1 cannot be reset.)
Reset completed or not requested (normal operation).
Default
FbEq 16
Output
power
... 36.15.
36.17
respectively.
0
1
3
4
6
7
8
10
11
12
13
14
16
-
36.01 PVL
2.00 s
100 = 1 s
Motor torque
36.40
... 36.49.
36.09
respectively.
100.00
1 = 1
Done
0

Hide quick links: