Default control connections for the ABB standard macro

This connection diagram is valid for the standard drive variant ACS380-04xS and the
configured drive variant ACS380-04xC +L538 (with the ABB standard macro
selected).
Terminals
Notes:
Terminal sizes: 0.14 mm² ... 1.5 mm²
Tightening torques: 0.5 N·m (0.4 lbf·ft).
Terminals DGND, AGND and SGND are internally connected to same reference
potential.
ghv Vertriebs-GmbH | Am Schammacher Feld 47 | 85567 Grafing | Telefon + 49 80 92 81 89 0 | info@ghv.de | www.ghv.de
Description
Digital I/O connections
Aux. +24 V DC, max 200 mA
Aux. voltage output common
Digital input common
Stop (0) / Start (1)
Forward (0) / Reverse (1)
Constant frequency / speed selection
Constant frequency / speed selection
Ramp set 1 input (0) / Ramp set 2 input (1)
Ready run output(0) / Not ready output (1)
Digital output auxiliary voltage
Digital input/output common
Analog I/O
Speed / freq.(0...10V)
Analog input circuit common
Not configured
Analog input circuit common
Output frequency (0...20 mA)
Analog output circuit common
Signal cable shield (screen)
3)
Ref. voltage +10 V DC
Safe torque off (STO)
Safe torque off. Connected at factory.
Drive starts only if both circuits are closed.
Relay output 1
No fault [Fault (-1)]
Control macros
33
1)
1)
2)
4)
4)