Download Print this page

System - ABB ACS380 Firmware Manual

Machinery control program
Hide thumbs Also See for ACS380:

Advertisement

ACS380 FW.book Page 330 Friday, May 4, 2018 4:18 PM
330 Parameters
No.
Name/Value
External 24V
95.15
Special HW settings
Bit
Name
0
Reserved
1
ABB Sine filter
2...15
Reserved
0...1
95.20
HW options word 1
Bit
Name
0
Supply frequency
60 Hz
1...12
Reserved
13
du/dt filter
activation
14...15 Reserved
0000h...FFFFh
96

96 System

96.01
Language
Not selected
English
Deutsch
Italiano
ghv Vertriebs-GmbH | Am Schammacher Feld 47 | 85567 Grafing | Telefon + 49 80 92 81 89 0 | info@ghv.de | www.ghv.de
Description
The drive control board is powered from an external
power supply.
Contains hardware-related settings that can be enabled
and disabled by toggling the specific bits.
Note: The installation of the hardware specified by this
parameter may require derating of drive output, or impose
other limitations. Refer to the hardware manual of the
drive.
Information
-
1 = An ABB sine filter is connected to the output of the drive/inverter
-
Hardware options configuration word.
Specifies hardware-related options that require
differentiated parameter defaults.
This parameter is not affected by a parameter restore.
Value
If you change the value of this bit, you have to do a complete reset to
the drive after the change. After reset you have to reselect the macro
to be used.
See section
Differences in the default values between 50 Hz and
60 Hz supply frequency settings
1 = 60 Hz.
When active, an external du/dt filter is connected to the drive/inverter
output. The setting will limit the output switching frequency, and
force the fan of the drive/inverter module to full speed.
0 = du/dt filter inactive.
1 = du/dt filter active.
Hardware options configuration word.
Language selection; access levels; macro selection;
parameter save and restore; control unit reboot; user
parameter sets; unit selection; parameter checksum
calculation; user lock.
Selects the language of the parameter interface and other
displayed information when viewed on the control panel.
Notes:
• Not all languages listed below are necessarily
supported.
• This parameter does not affect the languages visible in
the Drive composer PC tool. (Those are specified
under View – Settings – Drive default language.)
Select a language.
English.
German.
Italian.
Default
FbEq 16
1
-
1 = 1
-
on page 354. 0 = 50 Hz.
1 = 1
Not selected
0
1033
1031
1040

Hide quick links: