ACS380 FW.book Page 232 Friday, May 4, 2018 4:18 PM
232 Parameters
No.
Name/Value
32

32 Supervision

32.01
Supervision status
Bit
Name
0
Supervision 1 active
1
Supervision 2 active
2
Supervision 3 active
3
Supervision 4 active
4
Supervision 5 active
5
Supervision 6 active
6...15
Reserved
0000h...FFFFh
32.05
Supervision 1 function
Disabled
Low
High
Abs low
Abs high
Both
Abs both
Hysteresis
ghv Vertriebs-GmbH | Am Schammacher Feld 47 | 85567 Grafing | Telefon + 49 80 92 81 89 0 | info@ghv.de | www.ghv.de
Description
Configuration of signal supervision functions 1...3.
Three values can be chosen to be monitored; a warning or
fault is generated whenever predefined limits are
exceeded.
See also section
Signal supervision
(page 104).
Signal supervision status word.
Indicates whether the values monitored by the signal
supervision functions are within or outside their respective
limits.
Note: This word is independent of the drive actions
defined by parameters 32.06, 32.16, 32.26, 32.36,
and 32.56.
Description
1 = Signal selected by
32.07
1 = Signal selected by
32.17
1 = Signal selected by
32.27
1 = Signal selected by
32.37
1 = Signal selected by
32.47
1 = Signal selected by
32.57
Signal supervision status word.
Selects the mode of signal supervision function 1.
Determines how the monitored signal (see parameter
32.07) is compared to its lower and upper limits
and
32.10
respectively). The action to be taken when the
condition is fulfilled is selected by 32.06.
Signal supervision 1 not in use.
Action is taken whenever the signal falls below its lower
limit.
Action is taken whenever the signal rises above its upper
limit.
Action is taken whenever the absolute value of the signal
falls below its (absolute) lower limit.
Action is taken whenever the absolute value of the signal
rises above its (absolute) upper limit.
Action is taken whenever the signal falls below its low limit
or rises above its high limit.
Action is taken whenever the absolute value of the signal
falls below its (absolute) low limit or rises above its
(absolute) high limit.
Action is taken whenever the signal rises above the value
defined by the limit + 0.5 · hysteresis range
Supervision 1
hysteresis). The action is deactivated when
the signal falls below the value defined by the limit - 0.5 ·
hysteresis range.
Default
FbEq 16
0000h
32.46
is outside its limits.
is outside its limits.
is outside its limits.
is outside its limits.
is outside its limits.
is outside its limits.
1 = 1
Disabled
(32.09
0
1
2
3
4
5
6
7
(32.11