A5 Event Recorder; Event01 To Event40 - GE MOTOR MANAGEMENT RELAY 469 Instruction Manual

Table of Contents

Advertisement

5 ACTUAL VALUES

5.6 A5 EVENT RECORDER

S [ENTER] EVENT 01
No Event
GE Power Management
ð
TIME OF EVENT 01:
ENTER
00:00:00.0
ESCAPE
DATE OF EVENT 01:
ESCAPE
Jan. 01, 1992
MESSAGE
MOTOR SPEED DURING
ESCAPE
EVENT01: Low Speed
MESSAGE
TACHOMETER DURING
ESCAPE
EVENT01: 0 RPM
MESSAGE
A:
0 B:
0
ESCAPE
C:
0 A EVENT01
MESSAGE
MOTOR LOAD
ESCAPE
EVENT01: 0.00 x FLA
MESSAGE
CURRENT UNBALANCE
ESCAPE
EVENT01: 0%
MESSAGE
GROUND CURRENT
ESCAPE
EVENT01: 0.00 A
MESSAGE
A:
0 B:
0
ESCAPE
C:
0 A Diff. EV01
MESSAGE
HOTTEST STATOR
ESCAPE
RTD: 0°C EVENT01
MESSAGE
HOTTEST BEARING
ESCAPE
RTD: 0°C EVENT01
MESSAGE
HOTTEST OTHER
ESCAPE
RTD: 0°C EVENT01
MESSAGE
AMBIENT
ESCAPE
RTD: 0°C EVENT01
MESSAGE
Vab:
0 Vbc:
0
ESCAPE
Vca:
0 A EVENT01
MESSAGE
Van:
0 Vbn:
0
ESCAPE
Vcn:
0 A EVENT01
MESSAGE
SYSTEM FREQUENCY
ESCAPE
EVENT01: 0.00 Hz
MESSAGE
0
kW 0
kVA
ESCAPE
0
kvar EVENT01
MESSAGE
POWER FACTOR
ESCAPE
EVENT01: 0.00
MESSAGE
TORQUE
ESCAPE
EVENT01: 0.0 Nm
MESSAGE
469 Motor Management Relay
5.6 A5 EVENT RECORDER

5.6.1 EVENT01 TO EVENT40

Range: hour:minutes:seconds
Range: month day, year
Range: High Speed, Low Speed
Seen only if the Two-Speed feature is enabled
Range: 0 to 3600 RPM
Seen only if a Digital Input is programmed as Tachometer
Range: 0 to 100000 A
Range: 0.00 to 20.00 x FLA
Range: 0 to 100%
Range: 0.00 to 5000.0 A
Range: 0 to 5000 A
Seen only if Phase Differential CT is programmed
Range: –50 to 250°C, ---- (no RTD)
Seen only if at least 1 RTD is programmed as Stator
Range: –50 to 250°C, ---- (no RTD)
Seen only if at least 1 RTD is programmed as Bearing
Range: –50 to 250°C, ---- (no RTD)
Seen only if at least 1 RTD is programmed as Other
Range: –50 to 250°C, ---- (no RTD)
Seen only if at least 1 RTD is programmed as Ambient
Range: 0 to 20000 A
Seen only if VT Connection programmed as None
Range: 0 to 20000 A
Seen only if VT Connection programmed as Wye
Range: 0.00, 20.00 to 120.00 Hz
Range: –50000 to 50000 kVA
Seen only if VT Connection programmed as None
Range: 0.01 to 0.99 Lead or Lag, 0.00, 1.00
Seen only if VT Connection programmed as None
Range: 0 to 999999.9
Seen only if Torque Metering is Enabled
5
5-23