standard ABC, the system phase sequence setpoint may be used to accommodate this
rotation. This setpoint allows the 489 to properly calculate phase reversal and negative
sequence quantities.
PATH: SETPOINTS
S2 SYSTEM SETUP
SERIAL START/STOP
[ ]
INITIATION: Off
STARTUP INITIATION
MESSAGE
RELAYS (2-5): ----
SHUTDOWN INITIATION
MESSAGE
RELAYS (1-4): ----
SERIAL START/STOP
MESSAGE
EVENTS: Off
If enabled, this feature will allow the user to initiate a generator startup or shutdown via
the RS232/RS485 communication ports. Refer to GE publication number GEK-106495: 489
Communications Guide for command formats. When a startup command is issued, the
auxiliary relay(s) assigned for starting control will be activated for 1 second to initiate
startup. When a stop command is issued, the assigned relay(s) will be activated for 1
second to initiate a shutdown.
CHAPTER 5: SETPOINTS
SERIAL START/STOP
Range: On, Off
Range: Any Combination of Relays 2 to
5
Range: Any Combination of Relays 1 to
4
Range: On, Off
489 GENERATOR MANAGEMENT RELAY – INSTRUCTION MANUAL