ð
STANDARD OVERLOAD
ENTER
CURVE NUMBER: 4
ESCAPE
TIME TO TRIP AT
ESCAPE
1.01 x FLA: 17414.5 s
MESSAGE
TIME TO TRIP AT
ESCAPE
1.05 x FLA: 3414.9 s
MESSAGE
TIME TO TRIP AT
ESCAPE
1.10 x FLA: 1666.7 s
MESSAGE
TIME TO TRIP AT
ESCAPE
1.20 x FLA: 795.4 s
MESSAGE
TIME TO TRIP AT
ESCAPE
1.30 x FLA: 507.2 s
MESSAGE
TIME TO TRIP AT
ESCAPE
1.40 x FLA: 364.6 s
MESSAGE
TIME TO TRIP AT
ESCAPE
1.50 x FLA: 280.0 s
MESSAGE
TIME TO TRIP AT
ESCAPE
1.75 x FLA: 169.7 s
MESSAGE
TIME TO TRIP AT
ESCAPE
2.00 x FLA: 116.6 s
MESSAGE
TIME TO TRIP AT
ESCAPE
2.25 x FLA: 86.1 s
MESSAGE
TIME TO TRIP AT
ESCAPE
2.50 x FLA: 66.6 s
MESSAGE
TIME TO TRIP AT
ESCAPE
2.75 x FLA: 53.3 s
MESSAGE
TIME TO TRIP AT
ESCAPE
3.00 x FLA: 43.7 s
MESSAGE
TIME TO TRIP AT
ESCAPE
3.25 x FLA: 36.6 s
MESSAGE
TIME TO TRIP AT
ESCAPE
3.50 x FLA: 31.1 s
MESSAGE
TIME TO TRIP AT
ESCAPE
3.75 x FLA: 26.8 s
MESSAGE
TIME TO TRIP AT
ESCAPE
4.00 x FLA: 23.3 s
MESSAGE
TIME TO TRIP AT
ESCAPE
4.25 x FLA: 20.5 s
MESSAGE
469 Motor Management Relay
4.6 S5 THERMAL MODEL

4.6.3 OVERLOAD CURVE SETUP

Range: 1 to 15; Step 1
Message seen only if Standard Curve Style is selected.
Range: 0.5 to 99999.9 s; Step 1
Cannot be altered if Standard Curve Style is selected.
Range: 0.5 to 99999.9 s; Step 1
Cannot be altered if Standard Curve Style is selected.
Range: 0.5 to 99999.9 s; Step 1
Cannot be altered if Standard Curve Style is selected.
Range: 0.5 to 99999.9 s; Step 1
Cannot be altered if Standard Curve Style is selected.
Range: 0.5 to 99999.9 s; Step 1
Cannot be altered if Standard Curve Style is selected.
Range: 0.5 to 99999.9 s; Step 1
Cannot be altered if Standard Curve Style is selected.
Range: 0.5 to 99999.9 s; Step 1
Cannot be altered if Standard Curve Style is selected.
Range: 0.5 to 99999.9 s; Step 1
Cannot be altered if Standard Curve Style is selected.
Range: 0.5 to 99999.9 s; Step 1
Cannot be altered if Standard Curve Style is selected.
Range: 0.5 to 99999.9 s; Step 1
Cannot be altered if Standard Curve Style is selected.
Range: 0.5 to 99999.9 s; Step 1
Cannot be altered if Standard Curve Style is selected.
Range: 0.5 to 99999.9 s; Step 1
Cannot be altered if Standard Curve Style is selected.
Range: 0.5 to 99999.9 s; Step 1
Cannot be altered if Standard Curve Style is selected.
Range: 0.5 to 99999.9 s; Step 1
Cannot be altered if Standard Curve Style is selected.
Range: 0.5 to 99999.9 s; Step 1
Cannot be altered if Standard Curve Style is selected.
Range: 0.5 to 99999.9 s; Step 1
Cannot be altered if Standard Curve Style is selected.
Range: 0.5 to 99999.9 s; Step 1
Cannot be altered if Standard Curve Style is selected.
Range: 0.5 to 99999.9 s; Step 1
Cannot be altered if Standard Curve Style is selected.
4
4-29

Advertisement

Table of Contents
loading

Table of Contents