2ND M FUNCTION DATA
(1 to 4)
[Function]
When 2nd M function is specified, value following address "B" can be identified. The 2nd M function
data output from the controller is a max. 8-digit BCD code.
(Note 1) Select an address for the 2nd M function address from the setup parameters basic
specification parameter "#1170 M2name" A, B or C address that is not being used for
"#1013 axname" or "#1014 incax".
[Operation]
"2nd M function data" are updated when:
(1) "B (A, C)**" is specified in automatic operation (memory or MDI).
(2) "B (A, C)**" is executed by manual numerical command input.
Data remain unchanged even after "M function finish" signal (FIN1 or FIN2) is sent back. Data
cannot be cleared by "Reset" or "Emergency stop".
The 2nd M function data is issued in the following manner.
Signal name
2nd M function data 1
2nd M function data 2
2nd M function data 3
2nd M function data 4
[Cautions]
(1) Only one 2nd M function can be placed in one block. The latter code will be valid if more than
one code is commanded in one block.
B05
B15 ;
[Related signals]
(1) 2nd M function strobe (BFn: X654 to)
6. EXPLANATION OF INTERFACE SIGNALS
6.2 PLC Input Signals (Data Type: R***)
Signal
abbreviation
Register (1st part system)
R228, 229
R230, 231
R232, 233
R234, 235
Output to 2nd M function data 1
This 2nd M function data is invalid.
6-2-22
1st system
2nd system
R228, 229
R328, 329
3rd system