Programming (Ssd Download); Check All Loop Units - Panasonic EBL512 Operating Instructions Manual

Fire alarm system ebl512
Hide thumbs Also See for EBL512:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01457
Rev: -
19
19.1
Operating Instructions Fire alarm system EBL512, V2.7.x

Programming (SSD download)

The PC program Win512 is used for programming of the site specific
data (SSD) and to download it into the EBL512 control unit(s) and/or
1728, 1735 / 1736 & 1826 / 1828 units connected to an Ext. FBP/DU
interface board 1587.
Win512 version 2.7.x also has to be used for EBL512 G3 control
unit(s) connected in a TLON Network with EBL512 control unit(s),
i.e. a mixed system. In such a case the software EBL512 version
2.7.x and EBL512 G3 United version 2.7.x have to be used.
NOTE!
The function "Fault latching / No fault latching" is in
Win512 version 2.7.x a Control unit properties setting but in a mixed
system all control units have to have the same setting.
When the units are running, i.e. the power is turned on and the TLON
network is running, the SSD download can take place.
The PC has to be connected to the "D" connector J1 in an EBL512
control unit (main board 1556).
76
Start Win512.
Now you have to log on to the control unit.
In Win512 (menu "Tools" | "Download"), you select the unit(s) to
which the SSD is be downloaded.
the installation) will be automatically saved after the download.

Check All Loop Units

In the Win512 COM loop icon pop-up menu select "Check All Loop
Units". This function can be used after (or before) the download of
SSD. The function is as follows:
The control unit will find all units that are connected on the COM
loop. The addresses (0-127) will be reported to Win512. For all 430x
/ 33xx units and some of the other units, the type of unit will also be
reported. All differences compared to the Win512 SSD will be listed
in the Win512 log view and can be saved and/or printed out.
NOTE!
During this check the COM loop will be disconnected
75
In a mixed system it is not possible to connect to an EBL512 G3 control
unit.
76
It is very important that the two first digits in the EBL512 S/W version
and the Win512 version are the same, e.g. for EBL version 2.7.1 shall
Win512 version 2.7.x be used.
77
Access code for level 5 shall be entered via the PC (Win512).
78
In a mixed system SSD will also be downloaded to the selected EBL512
G3 control units.
After the download to a control unit an automatic
reset/restart will take place. A number of faults might then be generated, e.g.
due to not connected units. This will cause "heavy traffic" on the network,
which might affect (delay) the SSD download to the other units.
81
75
78
For security reasons the SSD (i.e.
77