Zone or Zone/Address (H2/B1)

When a whole zone is disabled, all alarm points within the zone will
be disabled except the addressable manual call points. (Not valid for
the Australian and New Zealand conventions.)
Alarm points can be individually disabled.
Text in display
H2 Disable or re-enable
B1 Zone or Zone/Address
B2 Output
B3 Output type
B4 Alarm devices
B5 Routing equipment
B6 Alert annunciation function
Escape
menu
Disable
Zone 000
Automatic re-enable:
Disable
Zone 000 address 00
Automatic re-enable:
No
Change type
of disablement
No
Change type
of disablement
96
Comments
According to chapter
"Access", see page 88.
- Via menu B1 can a
Zone or an alarm point
(Zone / Address) be
disabled.
- A time for automatic
re-enablement can be
set.
- Disabled zones and
alarm points are shown
in a Re-enable list.
Use the soft key
"
Change type of
" to toggle
disablements
between:
Zone 000 and
Zone 000..address 00.
Write the zone number
and address.
To set an automatic re-
"▼"
enable time press
"►".
and
Write the
(d
time
efault is current
time + 3 hours). Press
"
" to disable, which
will be indicated with
"√" and a beep. The
zone will directly be
shown in the Re-enable
list