6 - Parameter Descriptions
H23: Current Limit Level during Speed Search
Range:
Description:
H24 & H25: PI Gain During Speed Search
Range:
Description:
90
EX) Speed search during Instant Power Failure restart:
Input
Voltage
Frequency
Voltage
Current
Multi-function
output or
Relay
80-200% (Default: 100%)
This parameter limits the amount of current during speed search. The set
value is the percentage of the H33- [Motor rated current]. See H22 [Speed
Search Select].
0-9999
H24 [P Gain] is the proportional gain used for speed searching. Set this
value condsidering the load inertia set in H37. The default for this parameter
is 100.
H25 [I Gain] is the integral gain used for Speed search PI controller. Set this
value condsidering the load inertia set in H37. The default for this parameter
is 200.
t1
t2
H23