BENSHAW RSi GX Series Hardware Manual page 125

Sensorless vector variable frequency drive
Table of Contents

Advertisement

Range:
Description:
Range:
Description:
I52 & I53: FDT (Frequency Detection) Level & FDT Bandwidth
0 - 400Hz (Default: I52 - 30.00Hz, I53 - 10.00Hz)
I52 sets the target frequency used in parameters in I54. Cannot be set higher
than F21.
Related Functions: I54 (Multi-function Output)
0 - 18 (Default: 12)
This parameter sets the function of the MO open collector output.
Setting Range
Select
FDT-1
FDT-2
FDT-3
FDT-4
FDT-5
Overload (OL)
Inverter Overload (IOL)
Motor stall (STALL)
Overvoltage Trip (OV)
Low voltage trip (LV)
Inverter Overheat (OH)
Command loss
During Run
During Stop
During constant run
During speed searching
Wait time for run signal
input
Fault relay output select
Warning for cooling fan
trip
6 - Parameter Descriptions
I54: Multi-function Output Define (MO)
Display
0
Output frequency arrival detection
1
Specific frequency level detection.
2
Frequency detection with pulse.
3
Frequency detection 1 with contact closure.
4
Frequency detection 2 with contact closure.
5
Overload detection.
6
Inverter overload detection.
7
Stall prevention mode detection.
8
Over voltage detection.
9
Low voltage detection.
10
Overheat detection.
11
Lost command detection.
12
Inverter running detection.
13
Inverter stop detection.
14
Steady speed detection.
15
Speed search mode detection.
16
17
18
Description