0 - 1 (Default: 0)
This parameter activates the skip frequencies (see H11-H16).
0.1-400Hz
To prevent undesirable resonance and vibration on the structure of a
machine, this function locks out the resonance frequencies from operation.
Three different jump frequency ranges can be set. This jumping of
frequencies does not occur while accelerating or decelerating. It only occurs
during continuous operation.
Run frequency cannot be set within the range of H11 thru H16. The
frequency values of the low numbered parameters cannot be set above those
of the high numbered ones. Settable within the range of F21 and F23.
z Note: When the reference frequency is set inside the jump frequency, the
output frequency goes to the frequency marked by "_" symbol.
z Note: If one frequency jump range is required, set all ranges to the same
one range.
1-100% (40%)
When F2 is set to S-curve, this parameter shapes the beginning of the
S-curve for smooth acceleration and deceleration.
1-100% (40%)
When F2 is set to S-curve, this parameter shapes the end of the S-curve for
smooth acceleration and deceleration.
6 - Parameter Descriptions
H10: Skip Frequency Select
H11-H16: Frequency Jump
H17: S-Curve Accel/Decel Start Side
H18: S-Curve Accel/Decel End Side