6 - Parameter Descriptions

6.1

Drive Group

0.00: Frequency Command
Range:
Description:
ACC/dEC: Accel/Decel Time
Range:
Description:
Output Frequency
Max. freq.
Acc. Pattern
58
0 - 400 Hz. (Default 0.00)
This parameter sets the frequency that the drive is commanded to output,
when the drive is operating from the keypad. Frequency setting mode must
be set to 1.
Drive Mode:
During Stop
During Run
Multi-step operation
It cannot be set greater than F21- [Max frequency].
0-6000 sec. (Default: Accel -5.0 s., Decel -10.0s.)
The acceleration time sets the amount of time to reach the maximum
frequency upon a start command. The deceleration time sets the amount of
time to stop from the maximum frequency. During Multi-Accel/Decel
operation, this parameter serves as Accel/Decel time 0.
Time
Dec. Pattern
Parameter Display:
Frequency Command
Output Frequency
Multi-step frequency 0.
Related functions:
FU1-20 [Max freq]
FU2-70 [Ref freq for accel/decel]
FU2-71 [Accel/decel time scale]
I/O-12 to I/O-14 [Multi-function input terminal P1,
P2, P3]
I/O-25 to I/O-38 [Acc/dec time for step frequency]
FU-70: select the frequency to be targeted for
acceleration and deceleration [Max freq, Delta freq]
FU2-71: select the time scale. [0.01, 0.2, 1]
I/O-12 to I/O-14: set the terminal function of
P1,P2,P3 terminal outputs
I/O-25 to I/O-38: preset the accel/decel time
activated via multi-function inputs (P1,P2,P3)