BENSHAW RSi GX Series Hardware Manual page 85

Sensorless vector variable frequency drive
Table of Contents

Advertisement

Range:
Description:
Range:
Description:
50 ~ 200 [%] (Default: 150%)
This parameter sets the maximum current capable of flowing to the motor
continuously for 1 minute. The set value is the percentage of H33 [Motor
rated current, page 92]. It cannot be set below F52 [Electronic thermal level
for continuous, page 79]. The drive is tripped in 1 minute when 150% of
rated motor current set in H33 [Motor Rated Current] flows for 1 minute.
z Note: The set value is the percentage of H33 [Motor rated current, page
92].
50 -200% (Default: 100%)
This parameter is the current at which the motor can run continuously.
Generally, this value is set to '100%' and which means the rated motor
current set in H33. This value cannot be set higher than F51 [ETH 1min].
Load Current
[%]
[ETH 1 min]
[ETH cont]
60 sec
z Note: The set value is the percentage of H33 [Rated Motor Current).
6 - Parameter Descriptions
F51: Electronic Thermal Level for 1 minute
F52: Electronic Thermal Level for Continuous
Trip Time
79