BENSHAW RSi GX Series Hardware Manual page 51

Sensorless vector variable frequency drive
Table of Contents

Advertisement

Frequency setting via potentiometer & operating via the Run key
1
0.00
2
dru
3
1
4
0
5
dru
6
Frq
7
0
8
9
3
10
Frq
11
10.00
10.00
12
R
U
V
S
W
T
G
VR
V1
CM
Wiring
Apply AC input power to the drive.
When 0.00 is displayed, press the Up (p) key three times.
"drv" is displayed. Operating method is selectable.
Press the Ent (˜) key.
Check the present operating method ("1": Run via control terminal).
Press the Ent (˜) key and then Down (q) key once.
After setting "0", press the Ent (˜) key. When 0 is blinking, press the
Ent again.
"drv" is displayed after "0" is blinking. Operation method is set via the
Run key on the keypad.
Press the Up (p) key once.
Different frequency setting method is selectable.
Press the Ent (˜) key.
Check the present frequency setting method ("0" is run via keypad).
Press the Up (p) key three times.
After checking "3" (frequency setting via potentiometer), press the Ent
(˜) key.
"Frq" is displayed after "3" is blinking. Frequency setting is set via the
potentiometer on the keypad.
Turn the potentiometer to set to 10.0 Hz in either Max or Min direction.
Press the Run key on the keypad.
RUN lamp begins to blink with FWD lamp lit and accelerating
frequency is displayed on the LED.
When run frequency 10Hz is reached, 10.00 is displayed as shown left.
Press the STOP/RST key.
RUN lamp begins to blink and decelerating frequency is displayed on
the LED.
When run frequency is reached to 0Hz, Run and FWD lamp turn off and
10.00 is displayed.
Motor
Keypad
Freq.
Run key
STOP/RST key
Operating pattern
4 - Operation
10 Hz
45