BENSHAW RSi GX Series Hardware Manual page 92

Sensorless vector variable frequency drive
Table of Contents

Advertisement

6 - Parameter Descriptions
H19: Input/Output Phase Loss Protection
Range:
Description:
86
0-3 (Default: 0 Disabled)
This function is used to fault the drive output in case of input/output phase
loss of power input or drive output.
Display:
Function:
0
Disabled
1
Output Phase protection
2
Input Phase protection
3
Input/Output Phase Protection
Output Phase Loss Protection
Set H19 value to 1.
Output phase loss: The drive faults if there is a phase loss on the U,V and
W terminals.
Input phase loss: The drive faults if there is a phase loss in the R, S and T
input terminals.
Related Functions: H22-H25 [Speed Search]
Setting Range
2nd Bit
1st bit
0
0
0
1
1
0
1
1
Set H33 [Motor rated current] correctly. If the actual
motor rated current and the value of H33 are different,
output phase loss protection function may not function.
H19
00
Phase loss protection does not work.
01
Protect drive from output phase loss.
10
Protect drive from input phase loss.
11
Protect drive from input and output phase loss.
CAUTION
Description

Hide quick links:

Advertisement

Table of Contents
loading