BENSHAW RSi GX Series Hardware Manual page 151

Sensorless vector variable frequency drive
Table of Contents

Advertisement

Keypad
Protective Function
Display
EEP
Parameter save error
HWt
Inverter hardware fault
Communication
Err
Error
Remote keypad
rErr
communication error
Keypad error
COM
FAn
Cooling fan fault
ESt
Instant cut off
External fault A contact
EtA
input
Etb
External fault B contact
Operating method when
the frequency command
__L
is lost
8 - Troubleshooting & Maintenance
Description
Displayed when user-setting parameters fails to be
entered into memory.
Displayed when an error occurs in the control circuitry
of the drive.
Displayed when the drive cannot communicate with
the keypad.
Displayed when the drive and remote keypad do not
communicate with each other. It does not stop drive
operation.
Displayed after the drive resets the keypad when a
keypad error occurs and this status is maintained for a
certain time.
Displayed when a fault condition occurs in the drive
cooling fan.
Used for the emergency stop of the drive. The drive
instantly turns off the output when the EST terminal is
turned on.
Caution:The drive starts to regular operation when
turning off the EST terminal while FX or RX terminal
is ON.
When multi-function input terminal (I20-I24) is set to
19 {External fault signal input: A (Normal Open
Contact)}, the drive turns off the output.
When multi-function input terminal (I20-I24) is set to
19 {External fault signal input:B (Normal Close
Contact)}, the drive turns off the output.
When the drive operation is set via Analog input
(0-10V or 0-20mA input) or option (RS485) and no
signal is applied, operation is done according to the
method set in I62 (Operating method when the
frequency reference is lost).
145