BENSHAW RSi GX Series Hardware Manual page 93

Sensorless vector variable frequency drive
Table of Contents

Advertisement

Range:
Description:
Range:
Description:
0-1 (Default: 0)
This parameter is activated when DRV is set to 1 or 2 (Run/Stop via Control
terminal).
Display:
Function:
0
The drive requires the start command to open and reclose
upon power loss.
1
The drive will restart upon return of power if run
command is still active.
Particular attention must be directed to this function due
to potential hazard as motor starts to run suddenly upon
applying AC input power.
Input voltage
Frequency
Run
command
When H20 is 0
0 - 1 (Default:0)
This parameter is activated when DRV is set to 1 or 2 (Run/Stop via Control
terminal).
Display:
Function:
0
The drive requires the start command to open and reclose
upon a fault reset.
1
The drive will restart upon a fault reset if run command is
still active.
Particular attention must be directed to this function due to
potential hazard as motor starts to run suddenly upon applying
AC input power.
6 - Parameter Descriptions
H20: Power ON Start Select
CAUTION
H21: Restart After Fault Reset Selection
CAUTION
When H20 is 1
87