Specification; Performance Specification; Hardware Specification; Communication Specification - BENSHAW RSi GX Series Hardware Manual

Sensorless vector variable frequency drive
Table of Contents

Advertisement

7.2

Specification

7.2.1

Performance Specification

Communication Method
Transformation Form
Applicable Drive
Converter
Connectable Drives
Transmission Distance
7.2.2

Hardware Specification

Installation

Power Supply
7.2.3

Communication Specification

Communication Speed
Control Procedure
Communication System
Character System
Stop bit Length
Sum Check
Parity Check
7.3
Installation
7.3.1

Connecting the Communication Line

1) Connect the RS485 communication line to the drive's (S+), (S-) terminals of the control
terminals.
2) Connect the CM terminal among drives for stable communication.
3) Check the connection and turn ON the drive.
4) Install a repeater to upgrade the communication speed or longer than 1200mm
communication line is used. Repeater is required for upgrading communication quality
in the noise-high environment.
5) If the communication line is connected correctly set the communication-related
parameters as the following:
DRV-03 [Drive mode]: 3(RS485)
DRV-04 [Freq. mode]: 7(RS485)
I60 [Inv. Number]: 1~32 (If more than 1 drive is connected, be sure to use different
numbers for each drive)
I61 [Baud-rate]: 3 (9,600 bps as Factory default)
I62 [Lost Mode]: 0 - No action (Factory default)
I63 [Time-Out]: 1.0 sec (Factory default)
I59 [Comm. Prot]: 0 - Modbus-RTU
Item
RS485
Bus method, Multi drop Link System
RSi GX Series
RS232 converter
Max 31
Max. 1,200m (within 700m recommended)
Item
Use S+, S- terminals on control terminal block
Use Insulated power from the drive power supply
Item
19,200/9,600/4,800/2,400/1,200 bps selectable
Asynchronous communication system
Half duplex system
ASCII (8 bit)
Modbus-RTU: 2 bit
2 byte
None