5.2

Function Group 1 [FU1]

Code
Parameter Name
[FU1]
F0
Jump Code
F1
Run Prevention
F2
Acceleration Pattern
F3
Deceleration Pattern
F4
Stop Mode Select
F8
DC Brake Start Frequency
F9
DC Brake Wait Time
F10
DC Brake Voltage
F11
DC Brake Time
F12
DC Brake Start Voltage
F13
DC Brake Start Time
F14
DC Pulse at Start
F20
Jog Frequency
2
F21
Maximum Frequency
F22
Base Frequency
F23
Starting Frequency
F24
Frequency Limit Selection
3
F25
High Limit Frequency
F26
Low Limit Frequency
F27
Torque Boost Select
F28
Torque Boost in Forward
F29
Torque Boost in Reverse
F30
V/F Pattern
Setting Range
1-60
0 (Fwd/Rev Run
Disable)
1 (Forward Run
Disable)
2 (Reverse Run
Disable)
0 (Linear)
1 (S-Curve)
0 (Linear)
1 (S-Curve)
0 (Decel to Stop)
1 (DC-brake to Stop)
2 (Free-run to Stop)
0.1-60 [Hz]
0-60 [sec]
0-200 [%]
0-60 [sec]
0-200 [%]
0-60 [sec]
0-60 [sec]
0-400 [Hz]
40-400 [Hz]
30-400 [Hz]
0-10 [Hz]
0 (No)
1 (Yes)
0.1-400 [Hz]
0.1-400 [Hz]
0 (Manual)
1 (Auto)
0-15 [%]
0 (Linear)
1 (Square)
2 (User V/F)
5 - Parameter List
Factory
Adj. during
Default
run
1
Yes
0
No
None
0
No
Linear
0
No
Linear
0
No
Decel to Stop
5.00 [Hz]
No
0.1 [sec]
No
50 [%]
No
1.0 [sec]
No
50 [%]
No
0.0 [sec]
No
1.0 [sec]
No
10.00 [Hz]
Yes
60.00 [Hz]
No
60.00 [Hz]
No
0.50
No
0 (No)
No
60.00 [Hz]
No
0.50 [Hz]
No
0 (Manual)
No
2.0%
No
2.0%
No
0
No
(Linear)
Page
65
65
66
67
68
68
68
69
69
70
70
71
71
72
72
72
73
73
74
75
75
75
49