0 - 30sec. (Default: 10sec)
This parameter issues an alarm signal when the current has fallen below the
level in F54-[Overload warning level]. The alarm signal persists for
parameter F55-[Overload warning time] even though the current has
become the level below F54 (see I54, I55). The set value is a percentage of
H33 [Motor rated current, page 92].
Multi-function output terminal (MO-MG) is used as the alarm signal output.
To output the alarm signal, set I54 [Multifunction Output Define, page 119]
to 'OL'.
z Note: The drive is not tripped by this function, it is only a warning.
Related Functions: H33 [Rated Motor Current], I54 [Multi-function Output
Define]
Select one output terminal for this function between MO and 3AC.
If selecting MO as output terminal, set I54 to 5 [Overload:OL].
0 - 1 (Default: 1)
This parameter turns off the drive output when motor is overloaded.
Set F56 to 1.
Drive output is turned off when the motor is overloaded.
Drive output is turned off when excessive current flows to the motor for
F58 [Overload Trip Time].
30-200% (Default: 180%)
This parameter sets the amount of overload current. The value is the
percentage of H33- [Motor rated current].
The drive cuts off its output and displays fault message when the output
current persists over the F57 [Overload Trip Level] for the time of F58
[Overload Trip Time]. This function protects drive and motor from
abnormal load conditions.
Related Functions: H33 [Rated Motor Current, page 92].
6 - Parameter Descriptions
F55: Overload Warning Hold Time
F56: Overload Trip Select
F57: Overload Trip Level