BENSHAW RSi GX Series Hardware Manual page 114

Sensorless vector variable frequency drive
Table of Contents

Advertisement

6 - Parameter Descriptions
H91 & H92: Parameter Read/Write
Range:
Description:
Set H91 to "Yes" and
press Enter key to read
the parameters.
SET
RUN
RUN
ENT
V R
E FRE UEN
DR VE
108
0 - 1 (Default:0)
Used to read/write drive parameters when using an optional remote keypad.
This is useful when programming drives to have same parameter settings.
The keypad can read (upload) the parameter settings from one drive and can
write (download) them to other drives.
Take caution when Parameter write (H92) is executed. By
doing this, parameters in drive are cleared and parameters
in remote keypad are copied to the drive.
Parameter Read:
Move to parameter H91.
Press Enter (˜) key once. Keypad display will be 0.
Press Up (p) key once. Keypad display will be 1.
Press Enter (˜) key twice. Keypad display will be 1.
H91 is displayed when Parameter read is finished.
Parameter Write:
Move to parameter H92.
Press Enter (˜) key once. Keypad display will be 0.
Press Up (p) key once. Keypad display will be 1.
Press Enter (˜) key twice. Keypad display will be 1.
H92 is displayed when Parameter write is finished.
Æ
Move remote LED
keypad to the second
drive.
FWD
REV
STOP
RESET
CAUTION
Æ
Install the keypad into the next
drive and set H92 to "Yes". Then
press Enter to download the parameters.
SET
RUN
RUN
V R
E FRE UEN
FWD
REV
STOP
RESET
ENT
DR VE

Hide quick links:

Advertisement

Table of Contents
loading