3.6

Control Circuit Terminals

3A
3B
Terminal
P1-P8
Multi-function input terminal 1-8
CM
Common Terminal
Power Supply for external
VR
potentiometer
Input terminal for voltage operation Used for frequency reference and uses 0-10V for
V1
Input terminal for current operation Used for frequency reference and uses 0-20mA
I
Multi-function analog output
AM
terminal
Multi-function open collector
MO
output
Ground terminal for external power
MG
supply
24
24V external Power supply
Multi-function relay output A
3A
contact
Multi-function relay output B
3B
contact
3C
Common for multi-function relays
S+, S-
Communication port
z Note:
Tie the control wires no more than 15cm away from the control terminals. Otherwise, it
interferes with front cover reinstallation.
Use copper wires rated 600V, 75W and higher.
Use the recommended tightening torque when securing terminal screws.
When you use external power supply (24V) for multi-function input terminal (P1-P8),
terminals will be active above 12V level. Take caution not to drop the voltage below
12V.
MO MG 24 P1 P2 CM P3 P4
3C
P5
CM
Name
3 - RECEIVING AND INSTALLATION
P6
P7 P8 VR V1
Used for multi-function input.
Used for input signal common.
Used as power for the analog frequency setting.
Maximum output is +12V, 100mA, Potentiometer
1-5kohm.
input. Maximum input voltage: -12~+12V input.
input. Internal resistor:500W.
Analog/digital output (For external monitoring)
Max. output voltage: 11V, Max. output current:
100mA
Use after defining the multi-function output
terminal.
DC24V, 50mA,or less.
Maximum output current: 100mA
Activates when the protective function is
operating. AC250V 1A or less.
Fault: 3A-3C short (3B-3C open)
Normal: 3B-3C short (3A-3C open)
Communication port for MODBUS-RTU
communication.
Control Terminals
S- S+
I AM
Description
25