BENSHAW RSi GX Series Hardware Manual page 79

Sensorless vector variable frequency drive
Table of Contents

Advertisement

Range:
Description:
Range:
Description:
0 - 400 Hz (Default:60.00)
This parameter sets the high limit frequency. It cannot be set above F21
(Max. Frequency). It is only displayed when F24 (Frequency high/low limit
select) is set to 1. This setting is also valid when frequency setting is done
via keypad. When frequency setting is done via Analog input (voltage or
current input), the drive operates within the range of high and low limit
frequency as shown below.
Set F24 to 1.
Active run frequency can be set within the range of F25 and F26.
Freq.
High limit
freq.
Low limit
freq.
0
0.1 - 400 Hz (Default: 0.50Hz)
This parameter sets the low frequency (see parameter F25 for more
information).
6 - Parameter Descriptions
F25: Frequency High Limit
When freq. limit is not
selected
Max freq.
10V
V1(Voltage input)
20mA
I (Current input)
F26: Frequency Low Limit
73