5 - Parameter List
Code
Parameter Name
[FU1]
4
F31
User V/F Frequency 1
F32
User V/F Voltage 1
F33
User V/F Frequency 2
F34
User V/F Voltage 2
F35
User V/F Frequency 3
F36
User V/F Voltage 3
F37
User V/F Frequency 4
F38
User V/F Voltage 4
F39
Output Voltage Adjustment
F40
Energy Save Level
F50
Electronic Thermal Selection
Electronic Thermal Level for 1
1
F51
minute
Electronic Thermal Level for
F52
continuous
Electronic Thermal
F53
Characteristic selection (Motor
Type)
F54
Overload Warning Level
F55
Overload Warning Hold Time
F56
Overload Trip Select
F57
Overload Trip Level
F58
Overload Trip Time
F59
Stall Prevention Mode Select
F60
Stall Prevention Level
50
Setting Range
0-400 [Hz]
0-100 [%]
0-400 [Hz]
0-100 [%]
0-400 [Hz]
0-100 [%]
0-400 [Hz]
0-100 [%]
40-110 [%]
0-30 [%]
0 (No)
1 (Yes)
50-200 [%]
0 (Self-cool)
1 (Forced-cool)
30-150 [%]
0-30 [sec]
0 (No)
1 (Yes)
30-200 [%]
0-60 [sec]
000-111 (bit set)
Bit 0: during Accel.
Bit 1: during steady
speed
Bit 2: during decel
30-150 [%]
Factory
Adj. during
Default
run
15.00 [Hz]
No
25 [%]
No
30.00 [Hz]
No
50 [%]
No
45.00 [Hz]
No
75 [%]
No
60.00 [Hz]
No
100 [%]
No
100 [%]
No
0 [%]
Yes
0 (No)
Yes
150 [%]
Yes
100 [%]
Yes
0
Yes
Self-cool
150 [%]
Yes
10 [sec]
Yes
1 (Yes)
Yes
180 [%]
Yes
60 [sec]
Yes
000
No
150 [%]
No
Page