6 - Parameter Descriptions
I55: Multi-Function Relay Output
Range:
Description:
I56: Fault Relay Output
Range:
Description:
126
[During Speed Search]
MO-MG is CLOSED during the drive is speed searching.
[Wait time for run signal input]
MO-MGis CLOSED when the drive is ready and waiting for a run
command.
[Fault Relay Output Select]
The parameter set in I56 is activated. For example, if setting I55, I56 to 17
and 2, respectively, Multi-function output relay will become active when
trip other than "Low voltage trip" occurred.
[Warning for cooling fan trip]
Used to output alarm signal when H78 is set to 0(constant operation at
cooling fan trip).
0 - 18 (Default: 17)
This parameter sets the function of multi-function relay output. See
parameter I54 (Multi-function Output Define).
0 - 7 (Default:2)
This function is used to allow the fault output relay to operate when a fault
occurs. The output relay terminal is 30A, 30B, 30C where 30A-30C is
normal open contact and 30B-30C is normal close contact.
When 17 {Fault display} is selected in I54 and I55, Multi-function output
terminal and relay will be activated with the value in I56.
z Note: When several faults occurred at the same time, Bit 0 has the first
priority.