1 - INTRODUCTION
Basic Configuration
1.3

Connection of Peripheral Devices to the Drive

The following devices are required to operate the drive. Proper peripheral devices must be
selected and correct connections made to ensure proper operation. An incorrectly applied
or installed drive can result in system malfunction or reduction in product life as well as
component damage. You must read and understand this manual thoroughly before
proceeding.
6
Use the power supply within the
AC Source Supply
permissible range of drive input power
rating (Refer to page 10).
MCCB or Earth
Select circuit breakers with care. A large
leakage circuit
inrush current may flow in the drive at
breaker (ELB)
power on.
Install it if necessary. When installed, do
Magnetic
not use it for the purpose of starting or
Contactor
stopping. Otherwise, it could lead to
reduction in product life.
The reactors must be used when the power
factor is to be improved or the drive is
Reactors
installed near a large power supply system
(1000kVA or more and wiring distance
within 10m).
To operate the drive with high performance
for a long time, install the drive in a proper
Installation and
place in the correct direction and with
wiring
proper clearances. Incorrect terminal wiring
could result in the equipment damage.
Do not connect a power factor capacitor,
To motor
surge suppressor or radio noise filter to the
output side of the drive.