BENSHAW RSi GX Series Hardware Manual page 48

Sensorless vector variable frequency drive
Table of Contents

Advertisement

4 - Operation
Parameter Initialize
How to initialize parameters of all four groups in H93
H 0
1
1
2
3
3
03
4
5
93
H 93
6
0
7
1
8
H 93
9
H 0
10
z Note: This parameter is used to reset the drive to its factory defaults.
42
In H0, press the Enter (˜) key once.
Code number of H0 is displayed.
Increase the value to 3 by pressing the Up (p) key.
In 3, press the Left (t) key once to move the cursor to the left.
03 is displayed. 0 in 03 is active.
Increase the value to 9 by pressing the Up (p) key.
93 is set.
Press the Enter (˜) key once.
The parameter number is displayed.
Press the Enter (˜) key once.
Present setting is 0.
Press the Up (p) key once to set to 1 to activate parameter initialize.
Press the Enter (˜) key once.
Return to the parameter number after blinking. Parameter initialize has
been complete. Press the either Left (t) or Right (u) key.
Return to H0.

Hide quick links:

Advertisement

Table of Contents
loading