Operation with Keypad and Control Terminal
4.4

Operation with the Keypad and Control terminal

When the operation reference signal is given to the control terminal and the frequency
setting is given by the keypad, set the DRV-03 [Drive mode] to Fx/Rx-1, and set the
DRV-04 [Frequency mode] to the Keypad. The frequency reference signal is set from the
control terminal, and the forward, reverse, stop key of the keypad will be invalid.
1. Turn the power ON and set the operation and the frequency setting.
2. Set the drv [Operation Reference Source Selection] to Fx/Rx-1, and the Frq [Frequency
Reference Source Selection] to Keypad.
3. Turn ON the operation reference signal FX (or RX). Keypad LED (FWD key or REV
key) will turn ON.
4. Set the operating frequency with the keypad. Use the arrow keys and set the frequency
to 50.00Hz.
The motor will rotate at 50Hz. The LED (RUN) of the keypad will blink when the drive
is accelerating or decelerating.
5. Turn the operation reference signal FX (or RX) OFF. The LED (FWD of REV) of the
keypad will turn ON.
4.4.1

Operation with Control terminal

1. Turn the power ON and set the operation and the frequency reference to the control
terminal mode.
2. Set the drv [Operation Reference Source Selection] to Fx/Rx-1, and the Frq [Frequency
Reference Source Selection] to V1.
3. Set the analog frequency reference by turning the volume (frequency volume) slowly to
the right. The keypad will display the output frequency (50.00 Hz).
4. By slowly turning the volume (frequency volume) to the left will decrease the output
frequency. The drive will stop operating and the motor will come to a halt when the
frequency reaches 0.00Hz.
5. Turn OFF the operation reference signal FX (or RX).
4.4.2

Operation with Keypad

1. Turn the power ON and set the operation and the frequency reference to the keypad
operating mode.
2. Set the drv [Operation Reference Source Selection] to Keypad, and the Frq [Frequency
Reference Source Selection] to Keypad-1.
3. Use the arrow keys to set the operating frequency to 50.00Hz. When the drive is not
running the command frequency is displayed.
4. Press the RUN key. The motor will rotate and the keypad will display the output
frequency.
5. Press the STOP/RESET key. The motor will decelerate and come to a halt, and the
keypad will display the command frequency.
z Note: The user can also operate the drive by setting the operation reference signal from
the Keypad, and sending the frequency reference signal to the control terminal. (Set
DRV-03 [Drive mode] to "Keypad", and the DRV-04 [Frequency mode] to "V1".)
46