Range:
Description:
Output Frequency
Output Voltage
Stop Command
FX -CM
ON
[Stop Mode: 'Decel']
0 - 2 (Default: 0)
This parameter sets the stopping method for the drive.
Display:
Function:
0
Decelerate to stop
1
DC brake to stop
2
Free run to stop
Decel: The drive stops using the deceleration pattern. Select 0 in F30.
DC-brake: The drive stops with DC injection braking. The drive will output
a DC voltage when the frequency goes below the DC injection braking
frequency during deceleration (see F8-F11, page 68-69).
Free-run (Coast to stop): The drive stops outputting voltage immediately
when the stop signal is commanded.
Output Frequency
[DCBr Freq]
Time
Output Voltage
[DCBr Value]
Time
FX -CM
ON
Time
[Stop Mode: 'DC-brake']
6 - Parameter Descriptions
Output Frequency
Time
Output Voltage
t1: FUN -24
t2: FU N-26
Time
t1
t2
Stop Command
-
FX
CM
Time
[Stop Mode: 'Free-run']
F4: Stop Mode Select
Output cutoff
Time
Output cutoff
Time
Stop Command
ON
Time
67