Range:
Description:
Frequency Setting Mode 6
Set Frq code (Frequency Mode] of Drive Group to 6 (Frequency setting
via 0 ~ 10V + 0 ~ 20mA input).
Related code: I6 - I10, I11 - I15
Refer to Frequency setting via -10 ~ +10V voltage input + 0 ~ 20mA
input.
Frequency Setting Mode 7
Set Frq code (Frequency Mode] of Drive Group to 7 (Frequency setting
via RS 485 communication).
Related code: I59, I60, I61
Refer to Chapter 7, RS485 communication.
0 - 400 Hz
The drive outputs preset frequencies set in these codes according to the
multi-function terminals configured as 'Speed-L', 'Speed-M' and 'Speed-H'.
The output frequencies are decided by the binary combination of P1,P2,P3
configured in I/O-12 to I/O-17. Refer to the following table for the preset
frequency outputs.
Display:
Function:
St1
Sets multi-step frequency 1 during multi-step operation
(Default: 10.00Hz).
St2
Sets multi-step frequency 2 during multi-step operation
(Default: 20.00Hz).
St3
Sets multi-step frequency 3 during multi-step operation
(Default: 30.00Hz).
Select a terminal to give Multi-step frequency command among P1-P8
terminals.
If terminals P6-P8 are selected, set I22-I24 to 5-7 to give Multi-step
frequency command.
Multi-step frequency 0 is settable in Frq - [Frequency mode] and 0.00 -
[Frequency command].
Multi-step frequency 1-3 are set at St1-St3 in Drive group, while Step
frequency 4-7 are set at I30-I33 in I/O group.
Binary combination of P1, P2, P3
Speed-L
Speed-M
0
1
0
1
6 - Parameter Descriptions
St1 - St3: Multi-Step Frequency 1-3
Speed-H
0
0
0
0
1
0
1
0
Output
Step speed
frequency
DRV-00
Speed 0
DRV-05
Speed 1
DRV-06
Speed 2
DRV-07
Speed 3
61