F22: Base Frequency
Range:
Description:
F23: Start Frequency
Range:
Description:
F24: Frequency High/Low Limit Select
Range:
Description:
72
30 - 400 Hz (Default: 60.00Hz)
The drive outputs its rated voltage to the motor at this frequency (see motor
nameplate).
Consult with the motor manufacturer before exceeding the
base speed of the motor. Verify that the driven equipment
can operate at the maximum speed set.
0 - 10Hz (Default: 0.50 Hz)
The drive starts to output its voltage at this frequency. If a frequency is set
lower than this, 0.00 Hz is automatically set. For example, if F23 is set to
5Hz, the drive starts running when the reference frequency is 5Hz.
Output Voltage
Rate Voltage
Start
Frequency
0 - 1 (Default: 0)
This parameter activates the high and low frequency (see F25 & F26).
CAUTION
Output Frequency
Base
Maximum
Frequency
Frequency