BENSHAW RSi GX Series Hardware Manual page 107

Sensorless vector variable frequency drive
Table of Contents

Advertisement

Range:
Description:
No. Display
1
UPHF Switch above IGBT's U phase fault
2
UPLF Switch below IGBT's U phase fault
3
vPHF Switch above IGBT's V phase fault
4
vPLF
Switch below IGBT's V phase fault
Switch above IGBT's W phase fault
5
WPHF
6
WPLF Switch below IGBT's U phase fault
7
UWSF Output short between U and W
8
vUSF Output short between U and V
9
WvSF Output short between V and W
10
UPOF Ground fault at U phase
11
vPGF Ground fault at V phase
12
WPGF Ground fault at W phase
13
UPOF Output open at U phase
14
vPOF Output open at V phase
15
WPOF Output open at W phase
0 - 1 (Default:0)
This is the reference frequency for acceleration and deceleration. If a
decided accel/decel time from a frequency to a target frequency is required,
set this value to 'Delta freq'. For most applications, the Max. freq. setting is
appropriate.
Setting Range
Display
Select
Max freq
0
(F21)
Delta Freq
1
Accel/Decel time setting based on Operating Frequency:
Accel/Decel time is set at the ACC/dEC.
If you set H70 to 1 {Delta frequency}, Accel/Decel time is the time that it
takes to reach a target frequency from a steady state frequency.
6 - Parameter Descriptions
Fault Type
H70: Frequency Reference for Accel/Decel
Description
The Accel/Decel time is the time that takes to reach the
maximum frequency from 0 Hz.
The Accel/Decel time is the time that takes to reach a
target frequency from any frequency.
Diagnosis
Contact Benshaw sales
representatives.
Check for the short of
drive output terminal,
motor connection
terminal or the proper
motor connection.
Check for the ground
faults.
Check for proper
connection of the motor.
101