Commissioning

5.6 Local Control Test

WARNING
MOTOR START
Failure to ensure that the motor, system, and any
attached equipment are ready for start can result in
personal injury or equipment damage. Before start,
Ensure equipment is safe to operate under any
condition.
5
5
Ensure that the motor, system, and any
attached equipment are ready for start.
1.
Press [Hand On] to provide a local start command
to the adjustable frequency drive.
2.
Accelerate the adjustable frequency drive by
pressing [
of the decimal point provides quicker input
changes.
3.
Note any acceleration problems.
4.
Press [Off]. Note any deceleration problems.
In the event of acceleration or deceleration problems, see
chapter 7.5 Troubleshooting. See chapter 7.4 List of Warnings
and Alarms for resetting the adjustable frequency drive
after a trip.
32
®
VLT
] to full speed. Moving the cursor left
Danfoss A/S © 10/2014 All rights reserved.
AQUA Drive FC 202

5.7 System Start-up

The procedure in this section requires user-wiring and
application programming to be completed. The following
procedure is recommended after application set-up is
completed.
WARNING
MOTOR START
Failure to ensure that the motor, system, and any
attached equipment are ready for start can result in
personal injury or equipment damage. Before start,
Ensure equipment is safe to operate under any
condition.
Ensure that the motor, system, and any
attached equipment are ready for start.
1.
Press [Auto On].
2.
Apply an external run command.
3.
Adjust the speed reference throughout the speed
range.
4.
Remove the external run command.
5.
Check sound and vibration level of the motor to
ensure that the system is working as intended.
If warnings or alarms occur, see chapter 7.4 List of Warnings
and Alarms.
MG20MA22