6. Error handling
Error status 2

6.1.3 Restart communication between the bus node and the device

Problem description: X1 and X2 flash red simultaneously.The check of the mechanical
Remedy

6.1.4 Check fieldbus communication

Festo P.BE-CTEU-DN-OP+MAINT-EN en 1206NH
The load voltage supply for the connected device is missing
or exhibits undervoltage:
PS-LED flashes green
and
X1 and/or X2-LED flash green
Note
Requirement for diagnostics via LED display:
The connected device must support this diagnostic function.
(Additional information can be found in the respective device
description).
connection between bus node and device (dismantling/in-
stalling) effected no change. The fault cannot be eliminated in
this way.
Proceed as follows:
1. Disconnect the operating voltage.
2. Check, sever and re-establish the electrical connection
between the bus node and connected devices.
3. Restore voltage.
X1 and/or X2 illuminate or flash green.
Compare the desired baud rate with the baud rate set on
the bus node (DIL switch setting).
Compare the desired station number (NodeID) with the
station number set on the bus node (DIL switch setting).
6-5