5. Diagnostics
5.2.5 I/O-LED status display
IO= I/O status, connection status
LED display
Status/significance
– Normal operating status
– Communication with the controller
(PLC) OK
LED illuminated
– Bus node is in operational mode and
green
is controlled by the PLC
– IOs are controlled via the PLC via
fieldbus/network
– Operating status in preparation
– Bus node is in pre-operational mode
– Inputs/outputs (IOs) are in idle state
LED flashes
mode
green (1 Hz)
– Inputs/outputs (IOs) are in fail state
mode
– Typical cause:
LED illuminated
usually an unrecoverable software
red
fault, e.g. no bus voltage
– Inputs/outputs (IOs) are in fail state
mode
– PLC failure or stop
LED is flashing
– Incorrect station number in the PLC or
red
on the bus node (incorrect DIL switch
position)
– Fieldbus/network interruption or
message failure
– Fieldbus/I-port device not connected
– Commissioning of the bus node not
LED is off
complete or not successful
Tab. 5/6:
Status displays of the fieldbus/network-specific "IO" LED
Festo P.BE-CTEU-DN-OP+MAINT-EN en 1206NH
Error handling
–
–
•
Check voltage supply to bus
Section 2.2.3
•
Read device diagnostics via fieldbus
communication (if activated via DIL
switches on the bus node)
•
Eliminate displayed faults
•
Check PLC
•
Check station number
Note
Station number (Node ID) 0 is not
permissible!
•
Check fieldbus/network connection
•
Connect fieldbus/I-port device
•
Check fieldbus connection
•
Restart
5-9