5. Diagnostics

5.2.5 I/O-LED status display

IO= I/O status, connection status
LED display
Status/significance
– Normal operating status
– Communication with the controller
(PLC) OK
LED illuminated
– Bus node is in operational mode and
green
is controlled by the PLC
– IOs are controlled via the PLC via
fieldbus/network
– Operating status in preparation
– Bus node is in pre-operational mode
– Inputs/outputs (IOs) are in idle state
LED flashes
mode
green (1 Hz)
– Inputs/outputs (IOs) are in fail state
mode
– Typical cause:
LED illuminated
usually an unrecoverable software
red
fault, e.g. no bus voltage
– Inputs/outputs (IOs) are in fail state
mode
– PLC failure or stop
LED is flashing
– Incorrect station number in the PLC or
red
on the bus node (incorrect DIL switch
position)
– Fieldbus/network interruption or
message failure
– Fieldbus/I-port device not connected
– Commissioning of the bus node not
LED is off
complete or not successful
Tab. 5/6:
Status displays of the fieldbus/network-specific "IO" LED
Festo P.BE-CTEU-DN-OP+MAINT-EN en 1206NH
Error handling
Check voltage supply to bus
Section 2.2.3
Read device diagnostics via fieldbus
communication (if activated via DIL
switches on the bus node)
Eliminate displayed faults
Check PLC
Check station number
Note
Station number (Node ID) 0 is not
permissible!
Check fieldbus/network connection
Connect fieldbus/I-port device
Check fieldbus connection
Restart
5-9