4. Commissioning
4.2.4 Assign the I/O addresses of the participant (Standard EDS)
Festo P.BE-CTEU-DN-OP+MAINT-EN en 1206NH
You can assign the I/O addresses of the CPV Direct to the PLC
operands using the "Input" and "Output" tabs.
Fig. 4/4: Address assignment of the input (example)
CTEU-DN appears in the input data with two separate commu-
nication connections:
–
A "Strobed" connection for transmitting the 8 status bits
(diagnostic information).
–
A "Polled" or "Change of State" connection for transmit-
ting the physical input data.
4-9