Operating Mode; Control Mode; Real Time Clock; Table 6.5-1 Operation Mode - Siemens Argus 7SR21 Technical Manual

Overcurrent relay
Hide thumbs Also See for Argus 7SR21:
Table of Contents

Advertisement

6.5

Operating Mode

The relay has three operating modes, Local, Remote and Out of Service. The following table identifies the
functions operation in each mode.
The modes can be selected by the following methods: -
SYSTEM CONFIG>RELAY MODE setting, a Binary Input or Command
Table 6.5-1
Operation Mode
OPERATION
Control
Rear Ports
Fascia (Control Mode)
USB
Binary Inputs
Binary Outputs
Reporting
Spontaneous
IEC
DNP
General Interrogation
IEC
DNP
MODBUS
Changing of Settings
Rear Ports
Fascia
USB
Historical Information
Waveform Records
Event Records
Fault Information
Setting Information
6.6

Control Mode

This mode provides convenient access to commonly used relay control and test functions. When any of the items
listed in the Control Mode list are selected, control is initiated by pressing the ENTER key. The user is prompted
to confirm the action, again by pressing the ENTER key, before the command is executed.
Control Mode commands are password protected using the Control Password function – see section 6.9.
6.7

Real Time Clock

Time and date can be set either via the relay fascia using appropriate commands in the System Config menu, via
the data comms channel(s) or via the optional IRIG-B input. Time and date are maintained while the relay is de-
energised by a back up storage capacitor.
In order to maintain synchronism within a substation, the relay can be synchronised to the nearest second or
minute using the IEC 60870-5-103 protocol, optional IRIG-B input or binary input.
The default date is set at 01/01/2000 deliberately to indicate the date has not yet been set. When editing the
Time, only the hours and minutes can be edited. When the user presses ENTER after editing the seconds are
zeroed and the clock begins running.
Unrestricted ©2018 Siemens Protection Devices Limited
REMOTE MODE
Enabled
Disabled
Disabled
Setting Option
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Disabled
Enabled
Enabled
Enabled
Enabled
7SR210 & 7SR220 Description of Operation
LOCAL MODE
SERVICE MODE
Disabled
Enabled
Enabled
Setting Option
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Disabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Disabled
Disabled
Disabled
Enabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Page 93 of 94