Operate And Reset Time (46It) - Siemens Argus 7SR21 Technical Manual

Overcurrent relay
Hide thumbs Also See for Argus 7SR21:
Table of Contents

Advertisement

7SR21 & 7SR22 Performance Specification
Operate and Reset Level (46IT)
Attribute
I
Operate level
op
Reset level
Repeatability
Variation
2.7.5

Operate and Reset Time (46IT)

Attribute
Starter operate time (³ 2xIs)
t
Operate time
op
Reset time
Repeatability
Overshoot time
Disengaging time
Unrestricted Page 28 of 68
-10 °C to +55 °C
+ 2 Hz £ 5 %
f
- 3 Hz to f
nom
nom
char = IEC-NI,
IEC-VI,
IEC-EI,
IEC-LTI
char = ANSI-MI,
ANSI-VI,
ANSI-EI
char = DTL
ANSI DECAYING
t
res
Value
105 % Is, ± 4 % or ± 1% In
³ 95 % I
op
± 1 %
£ 5 %
Value
35 ms, ± 10 ms
K
=
´
t
Tm
, ± 5 % or ± 50 ms,
[ ]
op
a
I
-
1
Is
IEC-NI : K = 0.14, a = 0.02
for char =
IEC-VI : K = 13.5, a = 1.0
IEC-EI : K = 80.0, a = 2.0
IEC-LTI : K = 120.0, a = 1.0
é
ù
A
ê
ú
=
+
´
t
B
Tm
[ ]
op
ê
ú
P
I
-
1
ë
û
Is
for char = ANSI-MI : A = 0.0515, B = 0.114, P = 0.02
ANSI-VI : A = 19.61, B = 0.491, P = 2.0
ANSI-EI : A = 28.2,
, ± 1 % or ± 20 ms
t
d
R
=
´
t
Tm
, ± 5 % or ± 50 ms,
[ ]
res
2
-
I
1
Is
for char = ANSI-MI : R = 4.85
ANSI-VI : R = 21.6
ANSI-EI : R = 29.1
, ± 1 % or ± 20 ms
t
res
± 1 % or ± 20 ms
< 40 ms
< 60 ms
© 2013 Siemens Protection Devices Limited
, ± 5 % or ± 50 ms,
B = 0.1217, P = 2.0