Operate And Reset Level; Time Delayed Measured Earth Fault; Reference - Siemens Argus 7SR21 Technical Manual

Overcurrent relay
Hide thumbs Also See for Argus 7SR21:
Table of Contents

Advertisement

2.15 51G Time Delayed Measured Earth Fault

2.15.1 Reference

Parameter
Is
Setting
Char
Characteristic setting
Tm
Time Multiplier setting
t
Delay setting (DTL)
d
t
Reset setting
res
Applied current (for
I
operate time)

2.15.2 Operate and Reset Level

Attribute
I
Operate level
op
Reset level
Repeatability
-10 °C to +55 °C
Variation
f
nom
Unrestricted © 2013 Siemens Protection Devices Limited
Value
0.005, 0.006... 1.0 xIn
IEC-NI, -VI, -EI, -LTI;
ANSI-MI, -VI, -EI; DTL
0.025, 0.05... 1.6
0, 0.01... 20 s
ANSI DECAYING, 0, 1... 60 s
IDMTL
2 to 20 xIs
DTL
5 xIs
Value
105 % Is, ± 4 % or ± 1% In
³ 95 % I
± 1 %
£ 5 %
+ 2 Hz £ 5 %
- 3 Hz to f
nom
7SR21 & 7SR22 Performance Specification
op
Page 41 of 68