Cb Maintenance; Cb Counters - Siemens Argus 7SR21 Technical Manual

Overcurrent relay
Hide thumbs Also See for Argus 7SR21:
Table of Contents

Advertisement

3.9.

CB Maintenance

3.9.1.

CB Counters

Description
Gn CB Total Trip Count
Selects whether the CB Total Trip Count counter is enabled
Gn CB Total Trip Count Target
Selects the number of CB trips allowed before CB Total Trip
Count counter output operates
Gn CB Total Trip Count Reset
Resets CB Total Trip Count counter
Gn CB Total Trip Manual Open
Selects whether the CB Total Trip Manual Open is enabled
Gn CB Phase Trip Counters
Selects whether the CB Phase Trip Counters is enabled
Gn CB Ph A Trip Count Target
Selects the number of CB trips allowed before CB Ph A Trip
Count counter output operates
Gn CB Ph B Trip Count Target
Selects the number of CB trips allowed before CB Ph B Trip
Count counter output operates
Gn CB Ph C Trip Count Target
Selects the number of CB trips allowed before CB Ph C Trip
Count counter output operates
Gn CB E/F Trip Count Target
Selects the number of CB trips allowed before CB E/F Trip
Count counter output operates
Gn CB Delta Trip Count
Selects whether the CB Delta Trip Count counter is enabled
Gn CB Delta Trip Count Target
Selects the number of CB trips allowed before CB Delta Trip
Count counter output operates
Gn CB Delta Trip Count Reset
Resets CB Delta Trip Count counter
Gn CB Count To AR Block
Selects whether the CB Count To AR Block counter is enabled
Gn CB Count To AR Block Target
Selects the number of CB trips allowed before CB Count To
AR Block counter output operates. While count is above target
the Autorecloser will only perform 1 x Delayed Shot and
Lockout
Gn CB Count To AR Block Reset
Resets CB Count To AR Block counter
Gn CB Freq Ops Count
Selects whether the CB Frequent Operations Counter is
enabled
Gn CB Freq Ops Count Target
Selects the number of CB trips allowed before CB Frequent
Operations Counter output operates. While count is above
target the Autorecloser will only perform 1 x Delayed Shot and
Lockout
Gn CB Freq Ops Count Reset
Resets CB Frequent Operations Counter
Unrestricted ©2018 Siemens Protection Devices Limited
Range
Disabled, Enabled
0, 1 ... 9999, 10000
Disabled, Enabled
Disabled, Enabled
0, 1 ... 9999, 10000
0, 1 ... 9999, 10000
0, 1 ... 9999, 10000
0, 1 ... 9999, 10000
Disabled, Enabled
0, 1 ... 9999, 10000
Disabled, Enabled
0, 1 ... 9999, 10000
Disabled, Enabled
0, 1 ... 9999, 10000
7SR210 Settings Guide
Default
Disabled
100
Disabled
Disabled
100
100
100
100
Disabled
100
Disabled
100
Disabled
10
Page 57 of 61