Voltage Protection: Under/Over Frequency (81) - 7Sr22; Figure 3.16-1 Logic Diagram: Under/Over Frequency Detector (81) - Siemens Argus 7SR21 Technical Manual

Overcurrent relay
Hide thumbs Also See for Argus 7SR21:
Table of Contents

Advertisement

3.16 Voltage Protection: Under/Over Frequency (81) – 7SR22
Six under/over frequency elements are provided in the 7SR22 relay.
The relay utilises fundamental voltage measurement values for this function. The frequency calculation is based
on the highest input voltage derived from the voltage selection algorithm.
Frequency elements are blocked if all phase voltages fall below the 81 U/V Guard setting.
The sense of the element (under-frequency or over-frequency) is set by the 81-n Operation setting.
81-n Setting sets the pick-up voltage level for the element.
An output is given after elapse of the 81-n Delay setting.
The 81-n Hysteresis setting allows the user to vary the pick-up/drop-off ratio for the element.
Operation of the under/over frequency elements can be inhibited from: -
Inhibit 81-n
81-n U/V Guarded
81-n Element
Enabled
Disabled
Inhibit 81-n
Inhibit 81-n
81-n U/V Guarded
Yes
81 U/V Guard
Setting
<
<
<
VL1
VL2
VL3

Figure 3.16-1 Logic Diagram: Under/Over Frequency Detector (81)

Unrestricted ©2018 Siemens Protection Devices Limited
A binary or virtual input, function key or remote data Comms.
Under voltage guard element.
&
&
&
F
Voltage
Selection
7SR210 & 7SR220 Description of Operation
81-n Operation
81-n Setting
81-n Hysteresis
c
>
<
or
General Pickup
General Pickup
81-n Delay
81-n
81-n
Page 53 of 94