Operate And Reset Level; Operate And Reset Time; Instantaneous Measured Earth Fault; Reference - Siemens Argus 7SR21 Technical Manual

Overcurrent relay
Hide thumbs Also See for Argus 7SR21:
Table of Contents

Advertisement

2.11 50G Instantaneous Measured Earth Fault

2.11.1 Reference

Parameter
Is
Setting
i
Applied Current (for operate time)
t
Delay setting
d

2.11.2 Operate and Reset Level

Attribute
I
Operate level
op
Reset level
Repeatability
Transient overreach
(X/R £ 100)
Variation

2.11.3 Operate and Reset Time

Attribute
t
Element basic operate time
basic
t
Operate time following delay
op
Repeatability
Overshoot time
Disengaging time
Unrestricted © 2013 Siemens Protection Devices Limited
-10 °C to +55 °C
+ 2 Hz £ 5 %
f
- 3 Hz to f
nom
nom
7SR21 & 7SR22 Performance Specification
Value
0.005, 0.006... 25 xIn
From below Is to 2x Is & from below Is to 5x Is
0.00, 0.01...20.00, 20.50... 100, 101... 1000, 1010...
10000, 10100... 14400 s
Value
100 % Is, ± 5 % or ± 1% In
³ 95 % I
op
± 1 %
£ -5 %
£ 5 %
Value
Switched from 0 to 2x Is: 35 ms, ± 10 ms
Switched from 0 to 5x Is: 25 ms, ± 10 ms
, ± 1 % or ± 10 ms
t
+ t
basic
d
± 1 % or ± 10 ms
< 40 ms
< 50 ms
Page 33 of 68