Load Blinder (21LB – 1P)
3.9.1

Reference

Parameter
Φ
Angle + ve setting
Φ
Angle – ve setting
Z
Impedance
V
Vpps Level
pps
I
Izps Level
zps
3.9.2

Operate Level

Attribute
V
Voltage PPS operate level
PPS
Voltage PPS reset level
I
Current ZPS operate level
ZPS
Impedance
Repeatability
3.9.3

Operate Angle

Attribute
Operating angle
Unrestricted © 2013 Siemens Protection Devices Limited
Value
5 Deg to 85 Deg
5 Deg to 85 Deg
1 Ohm to 100 Ohms
1 V to 110 V
0.05 xIn to 5 xIn
Value
100 % Vs, ± 2 % or ± 0.5 V
110 % V
100 % Is, ± 5 % or ± 1% In
100 % Zs, ± 5 % or ± 0.1 Ω
± 1 %
Value
(21LB-1P Angle +ve°) ± 5° to (21LB-1P Angle –ve°) ± 5°
forward
(180° - 21LB-1P Angle +ve°) ± 5° to (180° + 21LB-1P Angle –ve°) ± 5°
reverse
7SR21 & 7SR22 Performance Specification
, ± 5 % Vn