27/59 Vx Under/Over Voltage; Reference; Operate And Reset Level; Operate And Reset Time - Siemens Argus 7SR21 Technical Manual

Overcurrent relay
Hide thumbs Also See for Argus 7SR21:
Table of Contents

Advertisement

7SR21 & 7SR22 Performance Specification
2.2

27/59 Vx Under/Over Voltage

2.2.1

Reference

Parameter
V
Setting
s
V
s
Guard Setting
Guard
hyst
Hysteresis setting
t
Delay setting
d
2.2.2

Operate and Reset Level

Attribute
V
Operate level
op
Reset level
Repeatability
Variation
2.2.3

Operate and Reset Time

Attribute
Element basic
t
basicE
operate time
t
Operate time following delay
op
Repeatability
Disengaging time
Unrestricted Page 22 of 68
Overvoltage
Undervoltage
-10 °C to +55 °C
+ 2 Hz £ 5 %
f
- 3 Hz to f
nom
nom
Overvoltage
Undervoltage
Value
5, 5.5...199.5, 200 V
1, 1.5, ...199.5, 200 V
0, 0.1... 80.0 %
0.00, 0.01...20.00, 20.50... 100, 101... 1000, 1010...
10000, 10100... 14400 s
Value
100 % Vs, ± 1 % or ±0.25 V
± 1 % or ± 0.25 V
= (100 % - hyst) x V
op,
± 1 % or ± 0.25 V
= (100 % + hyst) x V
op,
± 1 %
£ 5 %
Value
Switched from 0 to 1.1 xVs: 73 ms ± 10 ms
Switched from 0 to 2.0 xVs: 63 ms ± 10 ms
1.1 to 0.5 xVs: 58 ms ± 10 ms
, ± 1 % or ± 10 ms
t
+ t
basic
d
± 1 % or ± 10 ms
< 80 ms