7SR210 & 7SR220 Commissioning & Maintenance Guide
2.10 Over/Under Voltage
2.10.1 Phase Under/Over Voltage. (27/59)
I
L1
(I
)
A
I
L2
(I
)
B
I
L3
(I
)
C
I
4
(I
)
G
I
5
(I
)
SEF
V
L1
(V
)
A
V
L2
(V
)
B
V
L3
(V
)
C
V
4
(V
)
X
Voltage Inputs:
Current Inputs:
Disable:
Map Pickup LED:.
Where more than one Undervoltage (27) elements are being used with different settings, it is convenient to test
the elements with the lowest settings first. The elements with higher settings can then be tested without disabling
the lower settings.
Note that if the voltage is reduced below the 27UVG setting, the function may be blocked. VTS operation may
also block the 27 Undervoltage function. Current inputs are not normally required to stabilise the relay during
voltage element testing.
If the 'O/P Phases' is set to 'All', the voltage on all phases must be reduced simultaneously. Otherwise the 3
phases should be tested individually.
Page 48 of 82
37
50
49
(x2)
BF
37
50
49
(x2)
BF
37
50
49
(x2)
BF
46
46
60
NPS
BC
CTS
(x2)
50
37
BF
50
37
BF
NOTE: The use of some
functions are mutually exclusive
27
59
(x4)
27
47
59
(x2)
(x4)
27
59
(x4)
27
59
Optional
79
25
Figure 2.10-1
V
(V
), V
(V
), V
L1
A
L2
B
n/a apply zero current to stabilize other functions
47, 59N, 60VTS
27/59-n - Self Reset
7SR22
60
67/
67/
50
CTS-
51V
50
51
AFD
I
(x4)
(x4)
67/
67/
60
50
51V
50
51
CTS-
AFD
I
(x4)
(x4)
67/
67/
60
50
51V
50
51
CTS-
AFD
(x4)
(x4)
I
67/
67/
60
50N
51N
51c
VTS
(x4)
(x4)
67/
67/
50G
51G
(x4)
(x4)
67/
67/
64
50S
51S
H
(x4)
(x4)
81
(x6)
59N
74
(x2)
TCS
Phase Under/Over Voltage
(V
)
L3
C
© 2013 Siemens Protection Devices Limited
81
51c
HBL
2
81
51c
HBL
2
81
51c
HBL
2
81
HBL
2N
37G
(x2)
37S
(x2)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Argus 7sr22

Table of Contents