Current Protection: Measured Earth Fault (67G, 51G, 50G); Directional Control Of Measured Earth Fault Protection (67G) - 7Sr22; Figure 3.4.1-1 Logic Diagram: Measured Directional Earth Fault Protection - Siemens Argus 7SR21 Technical Manual

Overcurrent relay
Hide thumbs Also See for Argus 7SR21:
Table of Contents

Advertisement

3.4

Current Protection: Measured Earth Fault (67G, 51G, 50G)

The earth current is measured directly via a dedicated current analogue input.
All phase overcurrent elements can be set to measure either fundamental frequency RMS or True RMS current
i.e.
True RMS current: -
Fundamental Frequency RMS current: -
3.4.1
Directional Control of Measured Earth Fault Protection (67G) – 7SR22
The directional element produces forward and reverse outputs for use with measured earth fault elements. These
outputs can be mapped as controls to each shaped and instantaneous element.
If a protection element is set as non-directional then it will operate independently of the output of the directional
detector. However, if a protection element is programmed for forward directional mode then operation will occur
only for a fault lying within the forward operate zone. Conversely, if a protection element is programmed for
reverse directional mode then operation will occur only for a fault lying within the reverse operate zone. Typically
the forward direction is defined as being 'away' from the busbar or towards the protected zone.
The Characteristic angle is the phase angle by which the polarising voltage must be adjusted such that the
directional detector gives maximum sensitivity in the forward operate zone when the current is in phase with it.
The reverse operate zone is the mirror image of the forward zone.
The measured directional earth fault elements use zero phase sequence (ZPS) polarising.
Voltage polarisation is achieved for the earth-fault elements by comparison of the appropriate current with its
equivalent voltage: -
I
~ V
0
0
The characteristic angle can be user programmed to any angle between -95° and +95° using the 67G Char
Angle setting. The voltage is the reference phasor (V
the forward and reverse zones.
The centre of the forward zone is set by (V
Angle for maximum sensitivity e.g.
For fault current of -15
sensitivity, OR
For fault current of -45
sensitivity.
Minimum Polarising Voltage
The 67G Minimum Voltage setting defines the minimum polarising voltage level. Where the measured polarising
voltage is below this level no directional output is given and. Operation of protection elements set as directional
will be inhibited. This prevents mal-operation under fuse failure/MCB tripped conditions where noise voltages can
be present.
Figure 3.4.1-1
Unrestricted ©2018 Siemens Protection Devices Limited
50 Measurement = RMS
51 Measurement = RMS
50 Measurement = Fundamental
51 Measurement = Fundamental
) and the 67G Char Angle setting is added to this to adjust
ref
Angle + 67G Char Angle) and should be set to correspond with I
ref
°
°
(I lagging V by 15
) a 67G Char Angle of -15
°
°
(I lagging V by 45
) a 67G Char Angle of -45
Logic Diagram: Measured Directional Earth Fault Protection
7SR210 & 7SR220 Description of Operation
°
is required for maximum
°
is required for maximum
fault
Page 35 of 94